Billing terms
UK settlement intervals are usually 30 minutes. Maximum demand is therefore the highest half-hour average, not a single-cycle spike. Some meters can be set to 15 or 60 minutes; do not mix interval lengths when you compare sites.
MIC is a contract. Maximum demand is a measurement. A site can breach MIC (and pay excess capacity) without changing the contracted figure. VoltView reports both; it does not treat peak kW as a kVA capacity.
What VoltView returns
The peak-demand endpoints give you:
A high load factor means the site is using its peak steadily (process, refrigeration, always-on). A low load factor means a short spike and a lot of idle capacity — the usual case for offices, kitchens, and EV chargers.
Capacity on the contract is still in kVA. Convert only when you have power factor:
Diversity (ADMD)
Individual site peaks do not happen at the same minute. Diversity factor is:
If the four peaks are not coincident and diversity is 1.4:
How this hits the bill
Capacity is charged on the contracted MIC, in p/kVA/day, for every day of the period. It does not fall just because a quiet month had a low maximum demand. What does move the bill:What we do not do
- Treat
peak(kW) as MIC (kVA). - Collapse a portfolio to one ADMD unless you have asked for a coincident series, not a sum of site peaks.
- Size a transformer or a DNO application from VoltView alone. Use these figures as the measured input to that conversation.